MS21-H Soft Starter (High-performance)

KULUN MS21-H: bypass-type low-voltage AC motor soft starter with on-line monitoring, 5.5-630 kW for compressors, pumps, fans and crushers.

Mains Voltage RangeAC 110–440 V (mains)
Matched Motor Power5.5–630 kW

Features

  • CCC certified

  • Three starting modes: constant current, voltage ramp, pulse kick-start

  • On-line current monitoring with alarm

  • LED operating panel

Specifications

Input

Mains supply

AC 110–440 V, 45–65 Hz

Control supply

AC 220 V, 50/60 Hz

Output

Output type

Bypass type; external bypass contactor required

Rated range

5.5–630 kW

Operating characteristics

Starting modes

Constant current, voltage ramp, pulse kick-start

Duty

Short-time duty, max. 10 starts per hour

Key features

Stopping modes

Soft stop, coast stop

Start / stop time

1–120 s

On-line monitoring

Real-time motor current monitoring with overcurrent protection

Inputs

4 digital inputs (run, stop, jog, programmable)

Outputs

2 relay outputs (fault, bypass), NO contact, AC 240 V/3 A, DC 24 V/5 A

Communication

Modbus RTU

Current transformers

3 built in

Protection rating

IP20

Protection

Mains fault

Protection on mains frequency out of range, undervoltage or input phase loss

Phase imbalance

Protection when load current exceeds the imbalance threshold

Overheating

Protection when thyristor temperature > 85 °C

Overcurrent

Protection when output current reaches the set multiple

Motor phase loss

Protection when load current falls below the threshold setting

Typical Applications

The MS21-H is a bypass-type low-voltage AC motor soft starter with on-line current monitoring, 5.5–630 kW, with constant-current, voltage-ramp and pulse kick-start modes. Typical applications:

Heavy-load starts with current monitoring

Real-time motor current monitoring with overcurrent protection, for loads where start-up current needs to be supervised rather than assumed.

Pumps, fans and compressors

Adjustable 1–120 s start and stop ramps with soft stop or coast stop, up to 10 starts per hour; external bypass contactor required.

Drives integrated into a control system

4 digital inputs, 2 relay outputs and Modbus RTU for run, stop, jog, fault and bypass signals to a PLC or host system.

FAQ

How to confirm output voltage and current range?

AC 110–440 V (mains); 5.5–630 kW (matched motor power).

Which applications does it suit?

Three-phase AC motor drives — compressors, pumps, fans, crushers — with constant current, voltage ramp or pulse kick-start modes for heavy loads.

What information is needed for selection?

Site voltage, current, load type, control mode, installation conditions and process requirements.