Applications - KULUN Electric
Applications
Menu

Furnace Burn-Through: 170 V/8000 A SCR DC Power Supply

Conclusion: tapping one phase for furnace burn-through puts the whole load on that phase and leaves current to the operator’s eye. A 170 V/8000 A SCR DC power supply shares the duty across all three phases and holds current with a closed loop, backed by three-stage inverse-time current limiting. This article covers the tapping difference, the rectifier cabinet and the protection scheme.

The supply is a dedicated DC branch for tapping the taphole of an AC submerged arc furnace. It does not replace the three-phase electrode supply that runs the furnace.

Schematic of a three-phase AC supply feeding a thyristor rectifier, burn-through device and AC submerged arc furnace

What goes wrong when burn-through taps a single phase?

Conventional burn-through takes one phase from the AC three-phase supply and feeds it through the burn-through device. The wiring is simple, but the whole load lands on that one phase: its current jumps, the other two do not change, and the unbalance factor is pushed up by the burn-through duty alone.

The second problem is that current is not controlled. The impedance of the burn-through channel moves with temperature, burden and contact condition, and there is no closed loop on the AC side. Current swings with the operator’s judgement, and when a peak arrives the burn-through device overheats first.

How does an SCR DC supply share the load across three phases?

An SCR DC power supply is built from a main circuit, a control circuit and a cooling system. The main circuit contains the breaker, the thyristor rectifier assembly, fast fuses and a supply monitoring unit. DC output is taken from thyristors connected in parallel on the transformer secondary and delivered as D+.

All three phases enter the rectifier assembly through the transformer secondary, so the burn-through power is divided between them instead of resting on one. The incoming supply still follows grid and process conditions. AC phase current has to be referred through the transformer ratio and the rectifier connection, so no estimate is given here.

ItemConfiguration in this case
Main circuitBreaker, thyristor rectifier assembly, fast fuses, supply monitoring unit
DC outputParallel thyristors on the transformer secondary, D+ output
ControllerSiemens S7-200 SMART, local and remote control
Signal chainVoltage and current through isolated transducers into the PLC; voltage, current and power monitored
Status inputsMain circuit, cooling water, fast fuses, thyristor temperature
HMI and commsHMI on the cabinet door, Profinet

What does 170 V/8000 A mean in practice?

Rated capability follows P = U × I: 170 V × 8000 A = 1,360,000 W = 1360 kW, about 1.36 MW. That is the ceiling at rated voltage and rated current, not a constant power held through a whole burn-through. In constant-current mode the voltage follows channel impedance, so the actual power changes with it.

Worked example: 6000 A at 120 V channel voltage gives 720 kW. The figures show how to read the rating; they are not site measurements.

ItemParameter / configuration
ConstructionNon-explosion-proof, dry area at normal temperature
Rated output voltage170 V
Rated output current8000 A
CoolingWater-cooled
Control functionsLocal, remote, Profinet, constant current, three-stage inverse-time limiting
ProtectionShort circuit, water pressure, circulating water temperature, busbar temperature, controller board fault, system alarm and trip

How do constant current and three-stage limiting work together?

Output voltage and current pass through isolated transducers into the Siemens S7-200 SMART controller, which compares them with the current setpoint and adjusts the thyristor firing angle to bring current back. Current is measured, compared and corrected rather than watched on a meter.

Three-stage inverse-time limiting grades by overload level: the larger the overload, the shorter the permitted time, stepping current down or tripping the unit. Short-circuit protection covers the extreme fault; inverse-time limiting covers the band that is not yet a short circuit but should no longer continue. Both protect the burn-through device and the thyristor stack.

HMI screen of the burn-through rectifier supply for furnace 3, showing three-phase incoming voltage and current, output voltage and current, setpoint and circulating water data

The HMI on the cabinet door shows three-phase incoming voltage and current, output voltage, current, setpoint and power, plus thyristor opening and circulating water data. The same values reach the PLC and can be passed upstream over Profinet. Readings in the photograph are one moment in the field and are shown to illustrate the monitored items only.

What should be checked before installation?

  • Non-explosion-proof construction: install in a dry area at normal temperature, and treat the water circuit as part of the equipment.
  • DC burn-through is a separate branch; the three electrodes in the furnace stay on the original AC supply.
  • 8000 A is rated capability, not a recommended working point. Set constant current to the process and do not sit at the ceiling.
  • Water pressure, circulating water temperature, busbar temperature, thyristor temperature and fuse status are all interlocked into the PLC.
Burn-through DC power supply cabinet installed on site, with HMI and pushbuttons on the door and a guard rail beside it

The cabinet is installed indoors, with an HMI and pushbuttons on the door and a guard rail beside it. Internal configuration follows the design documents.

FAQ

Why does AC burn-through cause three-phase current unbalance?

Conventional burn-through uses one phase only, so the burn-through power sits on that phase while the other two carry their normal current. The unbalance factor rises because of the burn-through duty itself. With a DC supply the three phases share the duty, so unbalance no longer climbs for that reason alone.

How does an SCR DC supply stop the current from swinging?

Voltage and current are isolated and fed into the PLC, compared with the current setpoint, and the thyristor firing angle is adjusted until current returns to the setpoint. When channel impedance changes, the loop keeps correcting; the operator does not have to watch a meter and react.

What is the rated power of a 170 V/8000 A burn-through supply?

By P = U × I, 170 V × 8000 A = 1360 kW, about 1.36 MW. That is the rated point, not constant power throughout a burn-through. Under constant current the voltage follows channel impedance, so energy figures cannot be obtained by multiplying this power by burn-through duration.

How does three-stage inverse-time limiting differ from short-circuit protection?

Short-circuit protection answers the extreme fault and trips quickly. Three-stage inverse-time limiting grades the overload: the larger the overload, the shorter the time allowed before current is reduced or the unit trips. One covers the extreme case, the other the band that is not yet a short circuit but should not continue.

Timeliness note

This article is based on project material for a 170 V/8000 A SCR DC burn-through supply delivered by Sichuan Kulun Electric in November 2026, and applies to that model and to AC submerged arc furnace burn-through duty. Parameters for other furnace types and transformer connections have to be checked separately. Always follow the design documents, the manual and site measurements.

Need selection advice on Furnace Burn-Through: 170 V/8000 A SCR DC Power Supply?
Share your industry, load conditions, voltage, current, power range and site environment — Kulun engineers will help confirm the industrial power supply and control solution.
Inquiry
Leave your requirements and we will get back to you shortly. 24/7 service hotline (mobile): +86-183-8069-7622